Reasons for Temperature Rise During Power-On Operation of High-Voltage Switchgear
2025-12-12
After briefly familiarizing ourselves with high-voltage switchgear, let’s now explore together the reasons behind the temperature rise when high-voltage switchgear is energized and put into operation. I wonder if you’ll find this topic interesting? We’re wholeheartedly committed to providing you with high-quality service—let’s take a closer look!
(1) Different metals exhibit different thermal expansion effects. The coefficient of thermal expansion for steel bolts is significantly lower than that for copper or aluminum busbars. Particularly in bolt-type equipment connections, as the load current and temperature fluctuate during operation, the degree of expansion and contraction between the aluminum or copper and the iron will differ, leading to creep—a slow plastic deformation of the metal under stress. The creep process is also strongly influenced by the temperature at the connection point. Practice has shown that when the operating temperature at the connection exceeds 80°C, the metal at the connection will expand due to overheating, causing the contact surfaces to shift out of alignment and creating tiny gaps that promote oxidation. When the load current decreases and the temperature drops, returning to the original contact position, direct metallic contact between the surfaces becomes impossible due to the presence of an oxide film on the contact surfaces. Each cycle of temperature change increases the contact resistance, which in turn leads to greater heat generation in the next cycle. This increased temperature further degrades the operating conditions of the connection, thus setting off a vicious cycle.
(2) Data obtained from type tests are typically collected in a laboratory setting and involve relatively short durations—usually no more than 8 hours. These tests do not account for the cumulative temperature rise effect and therefore cannot be equated to the long-term operation of equipment that continuously generates heat.
(3) Improper tightening torque of fastening bolts at connection points. Some installation and maintenance personnel tend to believe that the tighter the connection bolts are tightened, the better—but this is actually not the case. Particularly with aluminum busbars, which have a low modulus of elasticity, once the bolt torque reaches a certain critical value, further excessive tightening—especially if the material strength is insufficient—can cause localized deformation and bulging on the contact surfaces, thereby reducing the actual contact area and increasing contact resistance, ultimately compromising the effectiveness of the conductor connections. Additionally, the electrical conductivity of the selected conductor materials often fails to meet the required specifications, mostly due to insufficient purity of the raw conductor materials.
(4) Other on-site factors, such as potentially improper installation and maintenance procedures—for example, during the processing, connection, and installation of busbars, inadequate or uneven surface treatment of the busbar contact surfaces, lack of smoothness, or failure to apply specialized electrical grease—can lead to a reduced effective contact area, increased contact resistance, and subsequent heating.