S11-M, S13-M, and S20-M Series Oil-Immersed Power Transformers
Category:
Keywords:
Product Description
- 产品描述
-
The 10kV and below S(Z)11, S(Z)11-M, and S13-M series oil-immersed transformers produced by our company are next-generation energy-saving products. They are widely used in power systems for 10kV and below lines, serving applications such as power transmission, transformation, distribution, power stations, power supply, lighting, and high- and low-voltage prefabricated substations.
Product Implementation Standard
GB 1094.1 "Power Transformers – Part 1: General Requirements"
GB 1094.2 "Power Transformers – Part 2: Temperature Rise"
GB 1094.3 "Power Transformers – Part 3: Insulation Levels, Insulation Tests and Air Clearances for External Insulation"
GB/T 6451 "Technical Parameters and Requirements for Three-Phase Oil-Immersed Power Transformers"
JB/T 10088 "Sound Level of Transformers Rated 6-220 kV"
GBT 25446 "Technical Parameters and Requirements for Oil-Immersed Amorphous Alloy Core Distribution Transformers"
Product Features
1. Employs corrugated-plate or plate-type radiator tanks with an aesthetically pleasing appearance.
2. A new suspension plate structure has been adopted, resolving the issue of the device body being “suspended in mid-air.”
3. Transformer oil is not exposed to the atmosphere, so there is no need for regular oil sample testing (in sealed systems).
4. Equipped with self-locking, anti-loosening nuts and featuring a non-core-hanging design, the unit’s body is tightly fitted to the oil tank, enabling it to withstand transportation vibrations and bumps.
5. The corrugated sheet not only has a cooling function but also a “breathing” function; its elasticity can compensate for changes in oil volume caused by temperature fluctuations.
6. No oil replacement is required throughout the normal service life, enhancing the safety and reliability of power grid operation.
Main Technical Parameters
Technical Parameters of 10kV-Class S(Z)11, S(Z)11-M, and S13-M Series Oil-Immersed Transformers
Rated Capacity (kVA)
Voltage combination
Connection Group Designation
No-load loss (W)
Load loss (W)
No-load current (%)
Short-circuit impedance (%)
Weight (kg) with load / without load
High voltage (kV)
High-voltage tap range
Low voltage (kV)
S11
S13
S11
S13
30
6, 6.3, 10, 10.5, 11
±5% or ±2 × 2.5% or ±4 × 2.5%
0.4
Dyn0 or Dyn11
100
80
630/600
1.5
2.1
4.0
295/495
50
130
100
910/870
1.3
2.0
4.0
390/590
63
150
110
1090/1040
1.2
1.9
4.0
450/650
80
180
130
1310/1250
1.2
1.8
4.0
510/710
100
200
150
1580/1500
1.1
1.6
4.0
550/750
125
240
170
1890/1800
1.1
1.5
4.0
660/860
160
280
200
2310/2200
1.0
1.4
4.0
760/960
200
340
240
2730/2600
1.0
1.3
4.0
900/1100
250
400
290
3200/3050
0.9
1.2
4.0
1090/1290
315
480
340
3830/3650
0.9
1.1
4.0
1235/1435
400
570
410
4520/4300
0.8
1.0
4.0
1510/1710
500
680
480
5410/5150
0.8
1.0
4.0
1740/1940
630
810
570
6200
0.6
0.9
4.5
2185/2385
800
980
700
7500
0.6
0.8
4.5
2550/2750
1000
1150
830
10300
0.6
0.7
4.5
2910/3110
1250
1360
970
12000
0.5
0.6
4.5
3460/3660
1600
1640
1170
14500
0.5
0.6
4.5
4020/4220
2000
1940
1550
18300
0.4
0.6
5.0
5480/5680
2500
2290
1830
21200
0.4
0.6
5.0
6010/6300
Message for inquiry